Product Details
Place of Origin: China
Brand Name: Calin
Certification: CE/SABS/IEC
Model Number: CA368
Payment & Shipping Terms
Minimum Order Quantity: Negotiation
Price: Negotiation
Packaging Details: Carton
Delivery Time: 30 days
Payment Terms: western Union,Paypal, T/T, L/C
Supply Ability: 70,000pcs per month
Product Name: |
LCD Display Three Phase Electricity Meter With Automatic Meter Reading System |
Standard: |
SANS1524-1 , IEC62056-21 , IEC62053-11 |
Dimensions: |
272x127x77mm |
Weight: |
2.5kg |
Display: |
LCD |
Accuracy: |
Class 1s |
Cover Type: |
Flush Straight |
Communication: |
PLC /RF/GSM/GPRS |
Product Name: |
LCD Display Three Phase Electricity Meter With Automatic Meter Reading System |
Standard: |
SANS1524-1 , IEC62056-21 , IEC62053-11 |
Dimensions: |
272x127x77mm |
Weight: |
2.5kg |
Display: |
LCD |
Accuracy: |
Class 1s |
Cover Type: |
Flush Straight |
Communication: |
PLC /RF/GSM/GPRS |
The CA368 is a three phase four-wire, compact design keypad based and STS token operated prepayment meter. It is in a compact BS housing and extrended transparent terminal cover. The meter is manufactured by ISO9001 standard with IP54 protection rating. Thanks to a wide range of power supply ( Un -40% +20%) and improved RF immunity withstand of 30V/m, it can operates in harsh environments.
The CA368 is ideal when separating accommodation; i.e. flats, apartments, houses offices where you have only one power supply. It is usually very expensive to pay a utility company to add extra supplies. Tiger Meters offer a low cost alternative and it allows you to keep control of your electricity usage.
Main Features
• 20 digit (Standard Transfer Specification) STS encryption
• Up to 13kV/6.5kA surge protection for lightening and other line surges
• IR optical & RS485 port allowing for easy data interrogation
• Disconnects on overload and no credit
• Programmable power limit and low credit warning
• Tamper detection and event record such as opening cover, reverse connection, black-out
• Dual power source working on both prepayment and credit mode
• Maximum demand measurement and load profiling (on request)
User Benefit
• Easy to install for both new reticulation and retrofitting due to BS mounting
• Low operational and inventory cost
• Can be ordered with PLC/ RF/ GPRS/GSM communication for AMR/AM I features
• Meter provides various valuable information by punching in Calin's short codes
• Flexible payment control setting
Specifications:
Electrical parameters: |
|
Nominal voltage Un |
3x240V |
Limited voltage |
60%~120%Un |
Frequency |
50/60Hz+5% |
Basic current(Ib) |
10A |
Maximum current(Imax) |
100A |
Starting current(Ist) |
30mA |
Active energy constant |
400imp/kWh |
Accuracy |
|
Active energy to IEC62053‐21 |
Class1.0 |
Reactive energy to IEC62053‐23 |
Class2.0 |
Power Consumption |
|
Power consumption in Voltage circuit |
<2W <8VA |
Power consumption in current circuit |
<1VA |
Temperature range |
|
Operation meter |
25℃ to+70℃ |
Storage |
40℃ to+85℃ |
|
|
Insulation strength |
|
AC Insulation strength |
4kV at 50Hz during 1min |
Impulse voltage 1.2/50μs mains connections |
8kV |
|
|
Electro Magnetic Compatibility |
|
Electrostatic discharges |
|
Contact discharge |
8kV |
Air discharge |
16kV |
Electromagnetic RF fields |
|
27MHz to 500MHz typical |
10V/m |
100kHz to 1GHz typical |
30V/m |
Fast transient burst test |
4kV |
Mechanical requirements |
|
Protection Rating |
IP54 |
Insulation Classification |
Protective Class II |
Maximum cable size |
10 mm |