Product Details
Place of Origin: China
Brand Name: Calin
Certification: STS, IEC
Model Number: CA168
Payment & Shipping Terms
Minimum Order Quantity: Negotiation
Price: Negotiation
Packaging Details: Carton
Delivery Time: 30 days
Payment Terms: western Union,Paypal, T/T, L/C
Supply Ability: 70,000pcs per month
Product Name: |
1 Phase 2 Wire STS Prepayment Electricity Meter |
Designed Life: |
15 Years |
Dimensions: |
155x120x52mm |
Constant: |
1000 Imp/kWh |
Accuracy: |
Class 1s Class 2s |
Tamper Protection: |
Cover Open , Reverse Connection , Earthing |
Networks: |
1Phase 2Wire/3 Wire |
Display: |
LCD |
Cover Type: |
Flush Straight |
Product Name: |
1 Phase 2 Wire STS Prepayment Electricity Meter |
Designed Life: |
15 Years |
Dimensions: |
155x120x52mm |
Constant: |
1000 Imp/kWh |
Accuracy: |
Class 1s Class 2s |
Tamper Protection: |
Cover Open , Reverse Connection , Earthing |
Networks: |
1Phase 2Wire/3 Wire |
Display: |
LCD |
Cover Type: |
Flush Straight |
Single Phase 2 Wire STS Prepaid Meters Emergency Credit Prapayment Enery Meter
Single Phase 2 Wire STS Prepaid Meters Emergency Credit Prapayment Enery Meter
Calin designs and produces prepaid electric meters which are cost-efficient and ideal for the use in solutions for AMR/AMI at residential as well as industrial applications.Calin's prepaid meters own anti-tamper features . The meter is built with multi sensors and triggers. including tamper shutdown protection ,disconnects on overload and no credit .
As tamper as the major cause of non-technical loss, Calin's prepaid meters are all provided with anti-tamper features. The meter is built with multi sensors and triggers. Any illegal intrusion will trigger visual and audio alarm and the inside contactor will disconnect the load if the user will not compromise within preset time period. The tamper will be recorded with a time stamp within meters' non-volatile memory as proof for future data collection.
Major Features
1) Display trip condition
2) Programmable under and over voltage trip
3) Significant reverse energy measurement SRE
4) Communication standards DL/T645-2007, 1200BPS for communication
5) Tamper shutdown protection
Key benefits
a) PLC/ RF / GPRS communication for AMR AMI features (On request)
b) Time of Use (TOU) , multi-rate, holiday setting
c) Easy and quick to install with exisiting wires
d) 15 year designed life
e) Enhanced revenue protection through flexible payment control
Specifications:
Nominal voltage Un |
220/230/240 V |
Limited voltage |
70%~120%Un |
Nominal frequency fn |
50-60Hz+5% |
Basic current(Ib) |
5-10A |
Maximum current(Imax) |
60-100A |
Starting current(Ist) |
20mA |
Active energy constant |
1000imp/kWh |
Accuracy as Active energy to IEC62053‐21 |
Class1.0 |
Power consumption in Voltage circuit |
<2W <8VA |
Power consumption in current circuit |
<1VA |
Operating temperature |
25℃ to+70℃ |
Storage temperature |
40℃ to+85℃ |
Insulation level |
4kV rms for 1min |
Impulse voltage withstand |
8kV, 1.2/50 μs |
Air discharge |
16kV |
Immunity to HF fields |
|
80MHz to 2GHz with load |
10V/m |
100kHz to 1GHz without load |
30V/m |
Fast transient burst test |
4kV |
Meter shell Protection Rate |
IP54(IEC60529) |
Insulation System Classification |
Protective Class II |